ZFP2M/X and derivatives
New
Warning: Last items in stock!
Availability date:
By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.
By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.
Blank Module
20 Zonal LEDs
40 Zonal LEDs
40 Zonal LEDs, Printer, 2 Keyswitches
Can't find what you're looking for? Need a panel with more Zonal LEDs, additional relays or extra sounder circuits? Why not build your own ZFP using our ZFP Medium Panel Selection Chart? Simply select the Switch & Indicator Module(s) and A-BUS PCB(s) you need and we'll do the rest - building, testing and shipping the panel to you in no time at all.
Approvals/certifications | Certified to EN54-2 & 4 by Intertek. |
Protocol/compatibility | Apollo XP95/Discovery. |
Mains supply | 230V 50/60Hz. |
Mains rated current | 1.35A maximum. |
Internal power supply | 27Vdc nominal. |
Total output current limited to | 5A @ 230Vac (Imax.A 4A; Imin. 12mA). |
Battery charge capacity | 7Ah min to 38Ah max. |
Quiescent current | Varies depending on the panel's configuration - refer to our ZFP loop/battery calculation tool for details. |
Max battery size and type | 2 x 12V 38Ah VRLA connected in series. |
No. of loop drivers | 2, 4, 6 or 8 (dependent on model purchased). |
Max. loop output current | 500mA (25V min; 34V max). |
Max. loop length | 1KM. |
Max. addressable devices per loop | 126. |
No. of conventional sounder circuits | 2 (Max. length per circuit is 500m). |
EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Max. sounder output current | 2 x 1A. |
Auxiliary relays | 2 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc. |
Other outputs | 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA. |
Auxiliary inputs | 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching). |
PC connection | Via a galvanically isolated USB socket on the Z41 control module. |
Pager/DECT connection | RS232. ESPA compatible. |
Graphics interface/diagnostics connection | RS485. Drax compatible. |
Network connection | RS485 hi-integrity multi-path fault tolerant network connection via optional ZHN network card. Max 128 network nodes (up to 64 main panels & 64 compact controllers). |
Indicators | Full-colour 480 x 272 pixel touchscreen, all relevant EN54 indicators plus 5 programmable indicators. Additional indicators dependent on Switch & Indicator module fitted. |
Controls | Interactive touchscreen with menu sensitive buttons; 1 x keyswitch allowing direct access to Access Level 2. Additional controls dependent on Switch & Indicator module fitted. |
Connections | Fixed, largest acceptable conductor size 1mm2. |
Expansion connections | RS485 peripheral bus connection allows the connection of up to 15 'A-Bus' PCBs (2 control cores plus screen plus 2 cores for power). |
Product dimensions (mm) | 450 W x 720 H x 200 D. |
Construction & finish | Light grey textured mild steel, 1.2mm Zintec. RAL7035 epoxy paint. |
IP Rating | IP30. |
Weight | TBC. |
Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |
1 Loop Variants | N/A. |
2 Loop Variants | ZFP2M/X (Blank Module). |
4 Loop Variants | ZFP4M/X (Blank Module). |
6 Loop Variants | ZFP6M/X (Blank Module); ZFP6M/20/X (20 Zonal LEDs); ZFP6M/40/X (40 Zonal LEDs); ZFP6M/40P/X (40 Zonal LEDs, Printer, 2 Keyswitches). |
8 Loop Variants | ZFP8M/X (Blank Module); ZFP8M/20/X (20 Zonal LEDs); ZFP8M/40/X (40 Zonal LEDs); ZFP8M/40P/X (40 Zonal LEDs, Printer, 2 Keyswitches). |
Product dimensions: | 450 W x 720 H x 200 D mm. |
Hole required for semi-flush mounting: | 456 W x 726 H x 195 D mm. Requires ZBEZM bezel. |
Optional ZBEZDM/SS Glazed Stainless Steel Frame and ZVWM Vision Window also available (see Accessories tab for details) |
"The advent of an easy-to-program fire panel with powerful capabilities is long overdue. I anticipate that the invention of the ZFP will revolutionise the fire industry by heralding a new era of touchscreen controlled 'super power' fire alarm technology."
STAN BROOKE, TECHNICAL ALARM SYSTEMS
Every once in a while a product comes along that lifts existing, respected technology to another level. C-TEC's ZFP is one such product.
Created with the input of some of the world's leading fire alarm and life safety experts, the ZFP is the powerful touchscreen controlled fire alarm panel that everyone's been waiting for.
Designed and built in the UK, the panel can be configured to suit any application. From small 'one out, all out' systems to large multi-loop networked systems with sophisticated cause and effects, the ZFP can handle them all – with ease.
"The look, feel and design of the ZFP's touchscreen is a big step-forward for end users, installers and service technicians alike. Accessing the panel's functions is simplicity itself and it includes a number of smart functions that help save valuable time."
PAUL WARD, PROCYON FIRE
Everything about the ZFP's unique full-colour touchscreen interface has been designed with the user in mind.
Simply tap the option you require and away you go. Whether you're the responsible person on site, the installer, the commissioning engineer or the emergency services, you can access the information you require quickly and easily - all at the touch of a virtual button.
Powerful diagnostics, rapid loop learn, 'SafeMode' and a unique 'DeviceManager' function combine to make the ZFP one of the most user friendly control panels on the market.
"The modular nature of the ZFP means I no longer need to worry about a design brief changing at the last minute. The risk of being stuck with a rigid, inflexible system has vanished. What's more, unplanned changes can be accommodated at a later date so the whole system is future proof."
GRAHAM BELL, SOLID STATE SECURITY
Mix and match is the name of the game with the ZFP and, with three master cabinets to choose from, you're spoilt for choice.
Depending on the cabinet you choose, extra indicator and switch modules can be added, along with additional loop driver PCBs, high-integrity network PCBs, 'A-BUS' peripheral PCBs, flush mounting bezels, glazed stainless steel frames and more.
With a wide range of 'off-the-shelf' ZFPs also available, getting the panel you need for a specific application has never been easier.
"The last thing our clients want after spending a fortune refurbishing their premises is an unsightly fire panel spoiling the space. The availability of a Compact Controller effectively gives our clients the best of both worlds – quality fire protection that looks well designed and integrated."
MARK DAVIES, K2 ARCHITECTS
With its classy Compact Controllers, the ZFP not only does the job, it looks the part too.
Worried that your plush new reception area is going to be compromised by an ugly metal box in the main entrance? Think again! The ZFP's optional state-of-theart
Compact Controllers are stylish, smart and can actually enhance the design of a building's reception area and access points. Simply locate the main panel out of sight and let the ZFP's modern high-tech Compact Controllers add a touch of class to your surroundings.
"The ZFP's 64 node peer-to-peer networking capacity is outstanding. It means that I can create a high integrity fire alarm and detection system with up to 12,800 zones and over 64,000 loop devices without compromising on quality. Superb!"
JOHN LLOYD, GLASSLETTER
Never before has networking a fire panel been so trouble-free.
Creating a sophisticated fire alarm system for an airport, hospital, university, tower block, hotel, football stadium or other large building is just a few steps up from establishing a simple 'one out, all out' system for a small factory unit.
Up to 64 eight-loop panels can be interconnected over the ZFP's high-integrity fault tolerant network. This versatility, coupled with the ability to assign individual zones across the network and add up to 38 characters of custom text per device means letting the emergency services know the precise location of a fire has never been easier.
"I don't make fire panels, I install them, but this is the fire panel I would have designedif I was an R&D engineer. The ZFP has virtually every feature you can think of and its touchscreen interface makes installation, commissioning and servicing very easy."
DAVID KEY, PHOENIX FIRE
For specialist installation companies and commissioning engineers, the ZFP has no equal.
Features such as a fully filterable 20,000+ event memory, optional paging facilities, powerful 500mA loop drivers with plug-on connectors, spacious cabinets with a 20-way earth bar, the ability to achieve up to 72 hours standby in a standard cabinet and intuitive PC programming tools combine to make the ZFP a very special fire panel indeed.
All this and full compliance with EN54 parts 2 and 4 means that the ZFP is rapidly becoming the fire panel of choice for the fire industry worldwide.