XFP 1 Loop 32 Zone Addressable Fire Panel View larger

XFP 2 Loop 32 Zone Addressable Fire Panel (XP95/Discovery protocol)

XFP502/X

New

C-TEC’s XFP two loop 32 zone addressable fire alarm panel offers high performance at a very competitive price.

LPCB certified to EN54 parts 2 & 4, it is supplied in durable metal enclosure, offers combined keypad or keyswitch entry to Access Levels 2 and 3 and is compatible with Apollo's XP95/Discovery protocol.

Ideal for use in small stand-alone applications or in larger applications due to its ability to sit on network of up to 8 XFP master panels, it is one of Europe's best-selling addressable fire panels.

Packed full of engineering features - please refer to the feature list below - the XFP502/X is also fully compatible with C-TEC’s Hush Button fire alarm solution and its new range of EN54 certified addressable sounders and VADs.

LPCB  CE

More details

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


More Information

  • Third-party certified to EN54-2/4 by the Loss Prevention Certification Board (LPCB).
  • Compatibility with Apollo's XP95/Discovery protocol.
  • Two independently programmable conventional sounder circuits.
  • Two programmable inputs.
  • A fault output relay and three programmable relay outputs with voltage free changeover contacts.
  • A selection of zone dependency/coincidence functions.
  • A day/night (building occupied/unoccupied) function.
  • An investigation delay period function.
  • Phased evacuation facility.
  • An alarm counter that records how many times the panel has been in alarm state.
  • Powerful short circuit protected loop drivers, capable of supporting up to 40 loop powered 10mA sounders per loop.
  • An integral EN54-4/A2 switch mode power supply.
  • Adjustable contamination levels.
  • Earth fault monitoring.
  • Combined keypad / keyswitch entry to Access Levels 2 and 3.
  • 999 event monitoring.
  • An intuitive Windows based upload-download PC program.
  • Optional flush-mounting bezel and glazed stainless steel enclosure also available.
  • Up to eight XFP main panels (any variant) can be connected onto a two-wire RS485 network. Alternatively, up to eight XFP repeaters can be connected to any non-networked main panel.

Technical Specifications

Approvals/certifications Certified to EN54-2 & 4 by the LPCB.
Protocol/compatibility Apollo XP95/Discovery.
Mains supply 230V 50/60Hz.
Mains rated current 680mA maximum.
Internal power supply 27Vdc nominal.
Total output current limited to 3A @ 230Vac (Imax.A 270mA; Imin. 70mA).
Quiescent current 100mA (2 loops unloaded).
Max battery size and type 2 x 12V 7Ah VRLA connected in series.
No. of loop drivers 2.
Max. loop output current 500mA (25V min; 34V max).
Max. loop length 1KM.
Max. addressable devices per loop 126.
No. of conventional sounder circuits 2 (Max. length per circuit is 500m).
EOL resistor value 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current 400mA.
Auxiliary relays 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Other outputs 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
Auxiliary inputs 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
PC connection PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.
Indicators 2 line x 40 character backlit display; 32 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault.
Connections Fixed, largest acceptable conductor size 1mm2.
Expansion connections 2-wire RS485 network/repeater connection available via optional AFP711 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network).
Product dimensions (mm) 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Construction & finish Metal.
IP Rating IP30.
Weight 4.5kg (without batteries).
Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.

Documentation

App Note 0002

How to set an Input Output Unit up on an XFP Fire Panel (DFU0000242 Rev 1)

Download (260.46k)

Accessories

12 other products in the same category:

Approval Certificates

Approval Certificate (LPCB)

Download

EC Certificate of Conformity (CPR)

Download

Declaration of Performance (C-TEC)

Download

Declaration of Conformity (C-TEC)

Download

Dimensions & Mounting Information

Product dimensions: 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Hole required for semi-flush mounting: 412 W x 255 H x 50 D mm. Requires AFP385 bezel

BIM/CAD Drawings

XFP502-X Flush mounted BIM (RFA)

Download

XFP502-X Surface mounted BIM (RFA)

Download