SAP501E/X Sprinkler Monitoring Panel View larger

SAP 1 Loop 16 Zone Addressable Sprinkler Monitoring Panel (XP95/Discovery protocol)

SAP501E/X

New

  • Ideal for monitoring up to 126 sprinkler flow switches.
  • One switch monitoring unit required per monitored flow switch.
  • Utilises the same technology as C-TEC's popular XFP addressable fire panel.
  • Up to 16 sprinkler zone indicators available (assignable via the panel’s PC programming tools).
  • Attractive flush or surface mountable plastic enclosure.
  • Combined keypad or keyswitch entry.

  CE

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

Protocol/compatibilityApollo XP95/Discovery.
Mains supply230V 50/60Hz.
Mains rated current350mA maximum.
Internal power supply27Vdc nominal.
Total output current limited to1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA).
Quiescent current50mA (loop unloaded).
Max battery size and type2 x 12V 3.2Ah VRLA connected in series.
No. of loop drivers1.
Max. loop output current500mA (25V min; 34V max).
Max. loop length1KM.
Max. addressable devices per loop126.
No. of conventional sounder circuits2 (Max. length per circuit is 500m).
EOL resistor value6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current400mA.
Auxiliary relays3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Other outputs24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
Auxiliary inputs2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
PC connectionPC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.
Indicators2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault.
ConnectionsFixed, largest acceptable conductor size 1mm2.
Expansion connections2-wire RS485 non-redundant network/repeater connection available via optional XFP761 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network).
Product dimensions (mm)380 W x 235 H x D 96mm;
Construction & finishPlastic lid and base; RAL7035 textured.
IP RatingIP30.
Weight1.8kg (without batteries).
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.

Accessories

12 other products in the same category:

Approval Certificates

Approval Certificate (LPCB)

Download

EC Certificate of Conformity (CPD)

Download

Declaration of Performance (C-TEC)

Download

Declaration of Conformity (C-TEC)

Download

Dimensions & Mounting Information

Product dimensions:380 W x 235 H x 96 D mm. 
Hole required for flush mounting:367 W x 220 H x 75 D mm. No bezel required.

BIM/CAD Drawings

XFP501E-X Flush mounted BIM (RFA)

Download

XFP501E-X Surface mounted BIM (RFA)

Download