XFP 1 Loop 32 Zone Addressable Fire Panel View larger

XFP 1 Loop 32 Zone Addressable Fire Panel (Hochiki ESP protocol)

XFP501/H

New

C-TEC’s XFP single loop 32 zone addressable fire alarm panel offers high performance at a very competitive price.

LPCB certified to EN54 parts 2 & 4, it is supplied in durable metal enclosure, offers combined keypad or keyswitch entry to Access Levels 2 and 3 and is compatible with Hochiki's ESP protocol.

Ideal for use in small stand-alone applications or in larger applications due to its ability to sit on network of up to 8 XFP master panels, it is one of Europe's best-selling addressable fire panels.

Packed full of engineering features - please refer to the feature list below - the XFP501/H is also fully compatible with C-TEC’s Hush Button fire alarm solution.

LPCB  CE

More details

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


More Information

  • Third-party certified to EN54-2/4 by the Loss Prevention Certification Board (LPCB).
  • Compatibility with Hochiki's ESP protocol.
  • Two independently programmable conventional sounder circuits.
  • Two programmable inputs.
  • A fault output relay and three programmable relay outputs with voltage free changeover contacts.
  • A selection of zone dependency/coincidence functions.
  • A day/night (building occupied/unoccupied) function.
  • An investigation delay period function.
  • Phased evacuation facility.
  • An alarm counter that records how many times the panel has been in alarm state.
  • Powerful short circuit protected loop drivers, capable of supporting up to 40 loop powered 10mA sounders per loop.
  • An integral EN54-4/A2 switch mode power supply.
  • Adjustable contamination levels.
  • Earth fault monitoring.
  • Combined keypad / keyswitch entry to Access Levels 2 and 3.
  • 999 event monitoring.
  • An intuitive Windows based upload-download PC program.
  • Optional flush-mounting bezel and glazed stainless steel enclosure also available.
  • Up to eight XFP main panels (any variant) can be connected onto a two-wire RS485 network. Alternatively, up to eight XFP repeaters can be connected to any non-networked main panel.

Technical Specifications

Approvals/certificationsCertified to EN54-2/4 by the LPCB (0832-CPD-0758).
Protocol/compatibilityHochiki ESP.
Mains supply230V 50/60Hz.
Mains rated current680mA maximum.
Internal power supply27Vdc nominal.
Total output current limited to3A @ 230Vac (Imax.A 250mA; Imin. 70mA).
Quiescent current80mA (loop unloaded).
Max battery size and type2 x 12V 7Ah VRLA connected in series.
No. of loop drivers1.
Max. loop output current500mA (25V min; 34V max).
Max. loop length1KM.
Max. addressable devices per loop126.
No. of conventional sounder circuits2 (Max. length per circuit is 500m).
EOL resistor value6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current400mA.
Auxiliary relays3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Other outputs24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
Auxiliary inputs2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
PC connectionPC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.
Indicators2 line x 40 character backlit display; 32 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault.
ConnectionsFixed, largest acceptable conductor size 1mm2.
Expansion connections2-wire RS485 network/repeater connection available via optional AFP711 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network).
Product dimensions (mm)410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Construction & finishMetal.
IP RatingIP30.
Weight4.5kg
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.

Documentation

App Note 0002

How to set an Input Output Unit up on an XFP Fire Panel (DFU0000242 Rev 1)

Download (260.46k)

Accessories

10 other products in the same category:

Dimensions & Mounting Information

Product dimensions: 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Hole required for semi-flush mounting:412 W x 255 H x 50 D mm. Requires AFP385 bezel

BIM/CAD Drawings

BIM Drawing (REVIT)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links
Back to links

CAD Drawing (DWG)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links
Back to links

Approval Certificates

Approval Certificate (LPCB)

Download

EC Certificate of Conformity (CPD)

Download

Declaration of Performance (C-TEC)

Download

Declaration of Conformity (C-TEC)

Download