Hi-Output IP65 Wall VAD c/w 103dB(A) Sounder (shallow base) View larger

Hi-Output W-2.4-8.2 IP55 Wall VAD c/w 103dB(A) Sounder

BF433A/CX/DR/65

New

  • An IP55 version of our popular W.2.4-8.2 Wall VAD & Sounder.
  • Provides 'W-2.4-8.2' light distribution when wall mounted (min 0.4 lux over a 2.4m x8.2m cuboid area) using the same lens and electonics as our EN54-23, 3 & 17 certified Hi-Output Sounder VAD.
  • Impressive 103dB(A) sound output @ 1m.
  • Onboard short-circuit loop isolator.
  • 550µA quiescent current.
  • 14mA alarm current @24V DC (VAD lit, sounder on max).
  • Group addressing facility allows multiple devices to be operated simultaneously.
  • 7 selectable volume levels and up to 15 selectable tone pairs.
  • IP55 rated.

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

Protocol/compatibility Compatible with C-TEC's XFP/ZFP XP95/Discovery Addressable Fire Panels.
Application/operation Designed to be wall mounted. Suitable for use in external areas where IP55 rated devices are deemed sufficient.
VAD category & coverage W-2.4-8.2.
Flash rate & colour 0.5Hz / White.
Supply/operating voltage 17 to 28V DC (Sounder); 21 to 28V DC (Sounder/VAD).
Quiescent current 550µA @ 24 VDC.
Nominal SPL (Sound Pressure Level) 103dB(A) when set to tone 1.
Alarm current 14mA (VAD lit, Sounder on max).
Indicators Polling (green LED) & Short Circuit Isolator Active (amber LED).
Product dimensions (mm) 114mm diameter x 131mm deep.
IP Rating IP55.
Weight 315g.
Operating conditions/temperature -10ºC to +55ºC. Max. 95% RH (Non-condensing).
Notes Includes the same lens and electronics as our EN54-23, 3 & 17 certified Hi-Output Sounder VAD but is IP55 rated.

Documentation

Hi-Output Sounder/VADs DoC

Declaration of Conformity (EMC/LVD) DOC0000058 Rev 1

Download (164k)

14 other products in the same category:

VAD coverage (with multiplication factors applied)

VAD coverage depends on factors such as ambient light and viewing angle (direct or indirect). The table below summarises how the coverage of the BF433A/CX/DR increases or decreases based on these factors. To use the table, calculate the lux level of the area requiring coverage, determine whether the viewing angle will be direct or indirect then read off the coverage in the relevant column. For further information refer to our VAD System Design Guide, downloadable from the Documentation tab below.

Lux level in area requiring coverage

W-2.4-8.2 Wall Mounted Direct Viewing

W-2.4-8.2 Wall Mounted Indirect Viewing W-4-4 Wall Mounted Direct Viewing W-4-4 Wall Mounted Indirect Viewing
000-101 lux 12.5m H x 42.6m W 4.3m H x 14.8m W 20.8m H x 20.8m W 7.2m H x 7.2m W
101-200 lux 10.6m H x 36.1m H 4.1m H x 13.9m W 17.6m H x 17.6m W 6.8m H x 6.8m W
201-300 lux 7.7m H x 26.2m W 3.4m H x 11.5m W 12.8m H x 12.8m W 5.6m H x 5.6m W
301-400 lux 5.5m H x 18.9m W 2.9m H x 9.8m W 9.2m H x 9.2m W 4.8m H x 4.8m W
401-500 lux 4.3m H x 14.8m W 2.4m H x 8.2m W 7.2m H x 7.2m W 4.0m H x 4.0m W
501-600 lux 3.1m H x 10.7m W 2.1m H x 7.4m W 5.2m H x 5.2m W 3.6m H x 3.6m W
601-700 lux 2.4m H x 8.2m W not applicable 4.0m H x 4.0m W 2.8m H x 2.8m W
701-800 lux not applicable not applicable 2.8m H x 2.8m W not applicable