SigTEL 16 Line Master Controller View larger

SigTEL 16 Line Master Controller

ECU-16

New

  • Coming soon - a new-look 16 line Master Controller for use with our SigTEL disabled refuge, fire telephone and stadium marshalling system.
  • Allows operators to communicate with up to 16 disabled refuge or fire telephone outstations.
  • Supplied with a backlit LCD and handset.
  • True duplex speech.
  • Unique ‘auto-learn’ facility allows fast system set up.
  • Can be semi-flush mounted using an AFP385 bezel.
  • Operation can be maintained for 24 hours (standby) and 3 hours (in use) using 2 x 12V 7 Ahr batteries.
  • Easily interfaced to NC951 accessible toilet alarms, PDA audio-frequency induction loop systems, strobes, CCTV activation relays, etc.
  • Improved networking capabilities coming soon allowing systems up to 224 lines and optional desk controllers - contact our sales desk for details.

CE

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

Approvals/certificationsFacilitates compliance with BS5839-9 when correctly installed.
Mains supply230V 50/60Hz.
Mains rated current500mA.
Internal power supply19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to1.5A @ 230Vac
Quiescent current100mA (controller with fault buzzer sounding) plus 1mA per Type A outstation and 3.2mA per Type B outstation.
Max battery size and type2 x 12V 7Ah VRLA connected in series.
No. of lines16 (note this unit is NOT compatible with our ECU-8S 8 line expansion unit).
Auxiliary relaysChangeover fault relay (failsafe). 30V 1A max.
Open collector outputs(OP1): Activates when the ECU is ringing; (OP2) Activates when there is an active accessible toilet alarm call; (OP3) Closes when the handset is off hook and remains active for 2 mins after it is replaced. 24V, 50mA max.
Other outputs+24 V. Typically used to supply power to equipment connected to the ECU's open collector outputs (relays, etc).
Engineer (AL3) functionsEngineer mode and reset buttons (internal).
Indicators128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on.
ControlsHandset; Scroll buttons; Hold; Call Accept; Function; Directory; Silence Buzzer.
Expansion connectionsIncreased network capability - details coming soon.
Product dimensions (mm)410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). Handset protrudes 80 mm beyond lid.
Construction & finishMetal lid and base, RAL7035 grey texture.
IP RatingIP20.
Weight3.1kg (without batteries).
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.

Accessories

8 other products in the same category:

Dimensions & Mounting Information

Product dimensions: 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). Handset protrudes 80mm beyond lid.
Hole required for semi-flush mounting:412 W x 255 H x 50 D mm. Requires AFP385 bezel.