SigTEL Schematic View larger

SigTEL 8 Line Master Controller (no handset)

ECU-8NT

New

  • Ideal for disabled refuge, fire telephone and stadium marshalling applications.
  • Does not include a handset - ideal for use on networked SigTEL systems that do not require multiple control points.
  • Can be connected to up to eight disabled refuge or fire telephone outstations.
  • Improved networking capability allow systems of up to 224 lines to be created with optional/additional desk unit control.
  • Supplied with a backlit LCD display.
  • Unique ‘auto-learn’ facility allows fast system set up.
  • Can be semi-flush mounted using an AFP385 bezel.
  • Operation can be maintained for 24 hours (standby) and 3 hours (in use) using 2 x 12V 7 Ahr batteries.
  • Easily interfaced to NC951 accessible toilet alarms, PDA range hearing loop systems, strobes, CCTV activation relays, etc.

CE

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

Approvals/certifications Facilitates compliance with BS5839-9 when correctly installed.
Mains supply 230V 50/60Hz.
Mains rated current 500mA.
Internal power supply 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to 1.5A @ 230Vac
Quiescent current 100mA (controller with fault buzzer sounding) plus 1mA per Type A outstation and 3.2mA per Type B outstation.
Max battery size and type 2 x 12V 7Ah VRLA connected in series.
No. of lines 8.
Auxiliary relays Changeover fault relay (failsafe). 30V 1A max.
Open collector outputs (OP1): Activates when the ECU is ringing; (OP2) Activates when there is an active accessible toilet alarm call; (OP3) Closes when the handset is off hook and remains active for 2 mins after it is replaced. 24V, 50mA max.
Other outputs +24 V. Typically used to supply power to equipment connected to the ECU's open collector outputs (relays, etc).
Engineer (AL3) functions Engineer mode and reset buttons (internal).
Indicators 128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on.
Controls Silence Buzzer. Other controls are available but are not applicable as no handset is provided on this unit.
Product dimensions (mm) 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Construction & finish Metal lid and base, RAL7035 grey texture.
IP Rating IP20.
Weight 3.1kg (without batteries).
Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.

Documentation

EVCS Control Panels DoC

Declaration of Conformity (EMC/LVD) DOC0000019 Rev 4

Download (203.22k)

8 other products in the same category: