BF562-5/E
New
Warning: Last items in stock!
Availability date:
By buying this product you can collect up to 21 loyalty points. Your cart will total 21 points that can be converted into a voucher of $4.20.
By buying this product you can collect up to 21 loyalty points. Your cart will total 21 points that can be converted into a voucher of $4.20.
PSU CUSTOMISATION
The BF562-5/E can be optionally customised to suit your exact requirements using a BF423 configurator and PC. Configurable parameters include Float voltage temperature compensation; Battery charge rate (mA); Battery impedance; Input/Output settings.
PSU STATUS LED (located on the PSU PCB)
1 flash = Mains Failure.
2 flashes = Battery Voltage Low.
3 flashes = Battery Voltage Critical.
4 flashes = Charger Failure.
5 flashes = Charger OK (Battery is either actively charging, or in float charge).
6 flashes = No Batteries Fitted (indicating DIP Switch 4 position).
7 flashes = Battery Resistance Fault (Level set by DIP Switch 2 position).
8 flashes = Output Over Voltage.
BATTERY FAULT MONITORING
The BF562-5/E monitors battery resistance to the requirements of EN54-4/A2. The fault threshold is directly related to the ability of the battery to deliver the rated current to the load. For example, batteries stored uncharged for long periods, during shipment and/or distribution, degrade leading to increased internal resistance. If a degraded battery is fitted, a fault will be shown by the PSU as mandated by EN54-4/A2.
DATA PORT
Data on the BF562-5/E's status can be extracted from the PSU's bi-directional data port. The data available includes thermistor measurements; battery terminal voltage; system voltage at load terminals; battery charge current; load current; battery impedance and ASCII text string status messages. Extracting this data requires additional equipment and permissions - contact C-TEC for details.
Approvals/certifications | Includes the same electronics as our EN54-4/A2 certified BF562-5 PSU |
Compatibility | *** Full compliance with all relevant standards must be checked by the responsible person with the caged PSU installed in a suitable enclosure *** |
Application/operation | An encased Mains to regulated DC switch-mode/digital hybrid power supply providing 5A @ 24V DC. It includes a single pole volt-free changeover relay that switches for any fault condition. User customisable via a BF423 Configurator. |
Mains supply | 230V 50/60Hz. |
Mains rated current | 1.3A r.m.s. |
Total output current limited to | 5A (Max. output current). |
Output | I max.a: 4.6A or 4A selectable. A load greater than I max.a will temporarily reduce batt. charging. I.max.b: 5A, charging turned off via CONN6. Output is also customisable via a BF423 Configurator*. |
Battery charge capacity | 2.5Ah up to 17Ah (battery charged to 80% capacity in 24hrs). Output is customisable via a BF423 Configurator to suit different manufacturers' batteries*. |
Max battery size and type | Up to 17Ah VRLA dependent on the size of the enclosure the BF562-5/E is mounted in. |
Indicators | Supply Present (Green); General Fault (Amber); Auxiliary Fault (Amber); Hazardous Voltages Present (Red). |
Connections | Mains Input (CONN1); Supply Output (CONN3); Battery Input (CONN3); Fault Relay (CONN4); Charge Off Input (CONN5). Battery Charge Current Link (PLK1); Battery Monitoring On/Off Link (PLK2); High Temp. Output (PL2). |
Expansion connections | A remote thermistor can be connected via PL3 terminals. |
Product dimensions (mm) | 143mm H x 173mm W x 66mm D. |
Construction & finish | Zintec base, polycarbonate cover. |
IP Rating | Dependent on mounting enclosure. |
Weight | 665g (without batteries). |
Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |
Notes | *Parameters configurable via a BF423 configurator are: Float voltage temp. compensation; Batt. charge rate (mA); Batt. impedance; Input/Output settings. |