Application/operation | A double gang Mains derived power supply c/w a conventional fire detector circuit. Provides 250mA @ 24V DC for powering up to 5 electromagnetic door retainers rated @ 50mA each. |
Mains supply | 230V 50/60Hz. |
Output | 250mA @ 21-28V DC. |
Indicators | Mains On (green); Output Triggered (red). |
Controls | Manual release via red button on PSU fascia. |
Connections | Mains supply terminal, Unswitched +V, Switched +V (for door retainer connection), 2 x 0V, Zone Trig (for fire detector/manual release button connection, fault monitored), Trig (for remote equipment connection). |
Product dimensions: | 147 W x 87 H x 39 D mm. Fits on a standard UK 25mm double gang flush or surface back box. |