Hush-Pro Landlord System Interface (CAST Protocol)

HP733/CA

New

  • Compatible with C-TEC's CAST protocol XFP and ZFP addressable fire panels.
  • Allows a stand-alone Hush-Pro domestic fire alarm system to be connected to a CAST landlord/communal system to unlock a series of powerful optional features such as remote off-site monitoring via the Cloud, automatic evacuation of dwellings in a Fire Level 2 condition, manual keyswitch evacuations by the fire and rescue services and more.
  • Visit our Domestic Fire Systems section for more information on Hush-Pro - a new approach to integrating domestic and communal/landlord fire alarm systems.

For availability details email hush-pro@c-tec.co.uk

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

Protocol/compatibilityC-TEC CAST (XFP & ZFP fire panels).
Power requirementsLoop powered (individual Hush-Pro Controllers/Systems are powered by their own PSUs).
Quiescent currentTBC.
IndicatorsLocal Fire (Fire Level 1), Global Fire (Fire Level 2), Fault (from Hush-Pro Controller) and Loop Fault.
Product dimensions (mm)146 W x 85 H x 21 D mm (Can be mounted on a standard UK 25mm double gang flush or surface back box).
Construction & finishSupplied on a double gang plastic plate.
IP RatingIP40.
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.
NotesMore detailed tech specs to follow.

Documentation

Accessories

Networked Hush-Pro Systems

To unleash the full power of Hush-Pro you can connect multiple stand-alone Hush-Pro systems to a communal C-TEC XFP or ZFP CAST protocol addressable fire alarm system (available 2019).

  • Use the Cause & Effect programming of the communal XFP or ZFP CAST fire panel to set-up building management approved phased evacuation scenarios that don't put peoples' lives at risk.
  • Program keyswitches at the communal CAST fire panel that allow the emergency services to evacuate groups of dwellings and/or floors of dwellings without having to climb staircases.
  • Report wiring faults, Fire Level 1 triggers (e.g. optical detector activated) and Fire Level 2 triggers (heat detector activated or optical detector activated for a prolonged pre-set period) to off-site monitoring centres to ensure potential dangers are reported in real time.

Hush-Pro Operation & Functions

  • When the Hush-Pro system is in its normal state, power is applied to its detection and alarm circuit which is continually monitored for open and short circuit faults.
  • When a fire detector within a dwelling triggers, the system's Alarm sounders and VADs will activate.
  • Depending on the system's configuration, a remote overdoor indicator outside the room and/or cooker shut-off relays may also activate.
  • If multiple Hush-Pro systems are connected to a compatible communal fire system, automatic phased evacuation, manual fire brigade evacuation and the off-site reporting of faults and fires may also be possible (see Networked HUSH2 Systems tab above for more details).

Some of the operational options available on Hush-Pro are:-

  • A HUSH/SILENCE FUNCTION
    Allows a hushed period of two minutes to be applied (and extended if required) for the management of false alarms
  • A 'HOT WORKS' FUNCTION
    Allows a hushed/isolation period of fifteen minutes to be applied (and extended if required) to protect against inadvertent activation.
  • A 'TEST' FUNCTION
    Allows the functionality of the system's detectors and alarm devices to be electronically tested with relevant faults indicated via the controller's fault status LED.

Summary of Hush-Pro features

  • Fully compliant with the latest revision of BS 5839-6 - upgrades the level of protection offered in a dwelling from the minimum Grade D requirement to Grade C.
  • Provides individual dwellings with an extendable two-minute silence facility and 15-minute isolate facility.
  • Mains powered via a separate double gang PSU with onboard 72 hour standby supply
  • Long-life replaceable Lithium Ion rechargeable battery (up to 12 years' life)
  • Wiring between all detection and alarm devices is fully open and short circuit monitored
  • Silence, Test and Fault Status indicators & controls can be viewed or operated at floor level and are therefore suitable for use by the elderly and disabled.
  • Four indicator LEDs - green Supply LED, yellow Fault LED, red Alarm LED and yellow Hushed LED.
  • Auxilliary interface connections to remote systems, e.g. communal fire alarm systems
  • Manufactured in the UK by one of the world's leading commercial fire system providers.

For a full list of features and benefits please download the Hush-Pro Key Advantages datasheet in the tab below.

Why use a Grade C system?

BS5839-6 GRADE C REQUIREMENTSBS5839-6 GRADE C REQUIREMENTS
Grade C systems require fault monitoring of the power supply.Grade D system power supplies can be completely unmonitored (Section 6.2 of BS5839-6 2013).
Grade C systems require fault monitoring of the interconnecting wiring.There is no monitoring of the wiring required in Grade D systems (Section 6.2 of BS5839-6 2013).
Grade C systems provide a readily accessible method of silencing and testing the system at floor level for compliance with Section 9.1.1 of BS 5839-6 2013Grade D systems require additional equipment to provide silencing facilities at floor level.