CFP708E-4
New
LPCB certified to EN54-2/4, C-TEC's CFP 8 zone economy fire alarm panel offers an array of user and installer-friendly features at a very competitive price.
Supplied in an attractive flush or surface mountable plastic enclosure, it includes eight detector zones, four conventional sounder circuits, class change and alert inputs, four open collector outputs (fire, fault, reset and remote) and combined keypad/keyswitch entry.
Unlike our Standard CFP fire panel, the CFP708E-2 is NOT compatible with CFP repeaters, relay expansion boards or EN54-13 interface cards. It also has limited engineering functions.
Warning: Last items in stock!
Availability date:
By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.
By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.
Approvals/certifications | Certified to EN54-2/4 by the LPCB (176b) / (0832-CPR-F0576). |
Mains supply | 230V 50/60Hz. |
Mains rated current | 350mA maximum. |
Internal power supply | 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault). |
Total output current limited to | 1.5A @ 230Vac (ImaxA eq 146mA). |
Quiescent current | 25mA (mains failed, internal sounder active, PSU & gen fault LED lit). |
Max battery size and type | 2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah. |
No. of detector zone circuits | 8 (Max. length per circuit is 500m). |
Call point resistor value | 470 to 680Ω. |
Max. devices per detector zone | 25 detectors (or 32 detectors/manual call points combined). |
No. of conventional sounder circuits | 4 (Max. length per circuit is 500m). |
EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Alarm voltage | 27V max, 20V min (final battery voltage). |
Max. sounder output current | 4 x 200mA (800mA total). |
Auxiliary relays | None. |
Open collector outputs | Four: (1) Aux. Fire; (2) Fault; (3) Reset (Active during reset cycle); (4) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltage 27Vdc). |
Other outputs | 24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed). |
Auxiliary inputs | Two: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching). |
Engineer (AL3) functions | Invoke One Man Walk Test; Program sounders to resound (or not resound) when a new zone enters alarm; Enter fault diagnostic facilities. |
Expansion connections | None. The CFP Economy panel CAN NOT be extended with CFP repeaters, relay cards or EN54-13 interface boards. |
Product dimensions (mm) | 380 W x 235 H x D 96mm. |
Construction & finish | Plastic lid and base; RAL7035 textured. |
IP Rating | IP30. |
Weight | 1.75kg (without batteries). |
Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |