CAST Hi-Output 100dB(A) Wall Sounder Deep View larger

CAST Hi-Output Wall Voice Sounder (deep base)

CA446A/DR

New

  • Superb sound intelligibility.
  • Onboard short-circuit loop isolator.
  • Four selectable volume levels.
  • Six selectable messages with tones.
  • 15.5mA typical alarm current (470µA typical quiescent current) @ 24-40V DC (sounder on max.)
  • Group addressing facility allows multiple devices to be operated simultaneously.
  • IP33C (Type B) rated.
  • Custom messages and CAST Lockdown Sounders also available to special order.

More details

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


More Information

'CAST' is the world’s most-advanced 'distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Now available to purchase, its key features include:

• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) - coming soon.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.

Technical Specifications

Protocol/compatibilityCompatible with C-TEC's CAST protocol Addressable Fire Panels.
Application/operationDesigned to be wall mounted. IP33C rated and suitable for use outdoors (note an IP65 rated version is also available).
Supply/operating voltage27 to 40V DC.
Quiescent current470µA typical.
Nominal SPL (Sound Pressure Level)100dB(A) @ 1m synchronised.
Alarm current15.5mA @ 27 to 40V DC (sounder on max).
IndicatorsPolling (red LED).
Product dimensions (mm)114mm diameter x 131mm deep.
IP RatingIP33C (Type B).
Weight300g.
Operating conditions/temperature-10ºC to +55ºC. Max. 95% RH (Non-condensing).