Approvals/certifications | Certified to EN54-3 & 23 by the LPCB. |
Protocol/compatibility | Compatible with C-TEC's CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on third-party panels is recommended before use) |
Application/operation | Designed to be ceiling mounted - either stand-alone with a red or white cap or as part of a stacked Sounder/VAD/Detector Base combination. |
VAD category & coverage | O-R-3-2.5-17 Rectangular coverage - ideal for corridor spaces. |
Flash rate & colour | 0.5Hz; 1Hz or OFF / White. |
Supply/operating voltage | 18 to 30V DC. |
Nominal SPL (Sound Pressure Level) | 96dB(A). |
Alarm current | At 30Vdc: 12.2mA (0.5Hz) or 19.5mA (1Hz); At 18Vdc: 14.5mA (0.5Hz) or 25mA (1Hz) |
Product dimensions (mm) | 122mm diameter x 46mm deep (not including optional detector and base). |
IP Rating | IP21C (Type A). |
Weight | 170g. |
Operating conditions/temperature | -10ºC to +55ºC. Max. 95% RH (Non-condensing). |
Notes | For compliance to EN 54-3 & EN54-23, the BF431QCP Quick Connect Plate must be used with the base device. |