ZHN Hi-Net Multi-Path Fault Tolerant Network PCB View larger

ZFP Hi-Net Multi-Path Fault Tolerant Network PCB

ZHN

New

  • Allows the interconnection of up to 64 ZFP Main Panels (any mix) and up to 64 ZFP Compact Controllers over a two-wire RS485 ring-wired, multi-path, fault-tolerant 'Hi-Net' network.
  • One ZHN required per ZFP Main Panel (ZFP Compact Controllers include a ZHN PCB as standard).
  • RS485 Protocol.
  • Max. cable length between nodes = 1KM
  • Max. cable length of entire network = 128KM
  • For retrofits, multiple ZHNs can be wired in a non-fault tolerant, single-path network configuration (Max. 8 nodes; Max length of entire network must not exceed 1KM).

CE

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

TypeRS485.
IndicatorsNetwork Status LEDs.
ConnectionsFrom node to node, connect A (IN) to A (OUT), B (IN) to B (OUT) and C (IN) to C (OUT). Terminals A and B are for data comms and terminal C is for earth screens.
Product dimensions (mm)TBC.
WeightTBC.
Network specificationMulti-path, fault-tolerant RS485. Max. 126 network nodes (up to 64 ZFP mains & 64 Compact Controllers); Max. cable length of network: 128km; Max. cable length between nodes: 1km. For standard non-fault tolerant network specs see main instructions.
NotesEach node requires a unique ID number (1-126) which is set via Dip switch (SW1) on the ZHN PCB.