Apollo Discovery 58000-600 Optical Smoke Detector View larger

Apollo Discovery 58000-600 Optical Smoke Detector

BF316DH

New

  • A high specification programmable opticial smoke detector with drift compensation.
  • Fully compatible with C-TEC's XFP & ZFP XP95/Discovery Addressable Fire Panels.
  • User programmable to operate in one of five sensivity modes (e.g. Mode 1 will give a higher senstivity to fire than Mode 5).
  • Works using the light scatter principle and responds well to slow-burning, smouldering fires.
  • Remote test feature.
  • Red LED illuminates when the detector is in alarm.
  • Certified to EN54-7 by the LPCB.
  • Requires a BF308XP standard base or BF308XPR low power relay base.
  • 'Xpert' card addressed for speedy installation.

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

Approvals/certificationsCertified to EN54-7 by the LPCB.
CompatibilityCompatible with C-TEC's XFP/ZFP XP95/Discovery Addressable Fire Panels.
Application/operationGenerates an alarm when it detects a pre-set threshold of smoke penetration in its smoke chamber. Provides a very good response to overheating/thermal combustion and a good response to smouldering/glowing/flaming combustion & flaming with high heat.
Application temperaturen/a
Static response temperaturen/a
SensitivityOption to select 5 different operating modes at the fire panel. See Operation Modes tab below for details.
Supply wiring2-wire, polarity insensitive.
Supply/operating voltage17 to 28V DC.
Quiescent current440µA.
Alarm current3.4mA (LED illuminated).
Indicators2 clear LEDs emitting red light when in alarm. Optional remote LED.
ConnectionsL1&L2 supply in/out; +R remote LED +Ve connection; -R remote LED -Ve connection. (5mA max. remote LED current @ 5V measured across remote load).
Product dimensions (mm)100mm diameter x 42 mm H (not in base). 50mm height when in base.
Construction & finishWhite polycarbonate UL94-VO. Nickel plated stainless steel terminals.
IP RatingIP44.
Weight105g (not in base); 160g (in base).
Operating conditions/temperature-40ºC to +70ºC.
NotesRequires a BF308XP standard base or BF308XPR low power relay base. 1mA power up surge current for 0.3 seconds.

Accessories

8 other products in the same category:

Operating Modes

The modes of operation for this detector, selectable from the XFP or ZFP control panel, are:-

ModeAlarm Threshold (%/m)dB/mMin. time to Alarm
11.40.065 seconds
21.40.0630 seconds
32.10.095 seconds
42.10.0930 seconds
52.40.115 seconds

Compensation rate complies with EN54-7.