24V 5A EN54-4 Switch Mode PSU View larger

24V 5A EN54-4 Switch Mode PSU

BF362-5

New

  • VDS certified to EN54-4 (1997/A2:2006).
  • Ideal for powering beam detectors, auto-dial communicators, aspirating smoke detectors, auto-open vent systems, auxiliary sounder systems or any other device performing a mandatory function of a fire alarm system.
  • Deep discharge battery protection and EN54 compliant reporting of battery impedance faults.
  • Includes a single-pole volt-free changeover relay that switches for any fault condition.
  • Three LED indicators - supply present, general fault and auxiliary fault (for optional connection to third-party equipment).
  • Link selectable battery charging capacity.
  • Environmentally-friendly charging circuit - dissipates just 0.35W compared to the industry norm of 2.55W.
  • Supplied in a tough, durable metal box.
  • Optional 'caged' and 'PCB-only' versions available with exactly the same electronics (order code BF362-5/E and BF362-5 respectively).

VDS  CE

By buying this product you can collect up to 21 loyalty points. Your cart will total 21 points that can be converted into a voucher of $4.20.


By buying this product you can collect up to 21 loyalty points. Your cart will total 21 points that can be converted into a voucher of $4.20.


Technical Specifications

Approvals/certificationsCertified to EN54-4 by the VdS (0786-CPR-20892) / (G09197)
Application/operationA boxed Mains to regulated DC power supply providing 5A @ 24V DC. Fully compliant with EN54-4, it includes a single pole volt-free changeover relay that switches for any fault condition.
Mains supply230V 50/60Hz.
Mains rated current1.35A maximum. (310 VA).
Total output current limited to5A (Max. continuous output current).
Output4.6A DC current or 4A DC current (I max a, if PLK2 link fitted), 1A charge current; 5A DC current (I max b, charging turned off).
Battery charge capacity7 Ah to 18 Ah.
Max battery size and type2 x 12V 18 Ah VRLA.
IndicatorsSupply Present (Green); General Fault (Amber); Auxiliary Fault (Amber); Hazardous Voltages Present (Red).
ConnectionsMains Input (CONN1); Supply Output (CONN5); Battery Input (CONN5); Fault Relay (CONN4); Charge Off Input (CONN4). Battery Monitoring On/Off Link (PLK1); Battery Charge Current Link (PLK2); High Temp. Output (PL2).
Product dimensions (mm)404 W x 404 H x 110 D mm.
Construction & finishMetal lid and base; RAL7035 textured.
IP RatingIP30 (designed for indoor use only).
Weight5.25kg (without batteries).
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.

Documentation

12 other products in the same category:

Dimensions & Mounting Information

Product dimensions:404 W x 404 H x 110 D mm. Designed for surface mounting only.

BIM/CAD Drawings

BF362-5 BIM (RFA)

Download

Approval Certificates

Approval Certificate (VDS)

Download

EC Certificate of Conformity (CPR)

Download

Declaration of Performance (C-TEC)

Download

Declaration of Conformity (C-TEC)

Download