24V 1.5A EN54-4 Switch Mode PSU View larger

24V 1.5A EN54-4 Switch Mode PSU

BF360-24

New

  • VDS certified to EN54-4 (1997/A2:2006).
  • Ideal for powering beam detectors, auto-dial communicators, aspirating smoke detectors, auto-open vent systems, auxiliary sounder systems or any other device performing a mandatory function of a fire alarm system.
  • Deep discharge battery protection and EN54 compliant reporting of battery impedance faults.
  • Includes a single-pole volt-free changeover relay that switches for any fault condition.
  • Three LED indicators - supply present, general fault and auxiliary fault (for optional connection to third-party equipment).
  • Link selectable battery charging capacity.
  • Environmentally-friendly charging circuit - dissipates just 0.35W compared to the industry norm of 2.55W.
  • Optional 'caged' and 'PCB-only' versions available with exactly the same electronics (order code BF360-24/E and BF360-24/C respectively).

VDS  CE

By buying this product you can collect up to 21 loyalty points. Your cart will total 21 points that can be converted into a voucher of $4.20.


By buying this product you can collect up to 21 loyalty points. Your cart will total 21 points that can be converted into a voucher of $4.20.


Technical Specifications

Approvals/certificationsCertified to EN54-4 by the VdS (0786-CPD-20672) / (G208156)
Application/operationA boxed Mains to regulated DC power supply providing 1.5A @ 24V DC. Fully compliant with EN54-4, it includes a single pole volt-free changeover relay that switches for any fault condition.
Mains supply230V 50/60Hz.
Mains rated current350mA maximum. (80.5 VA)
Total output current limited to1.5A (Max. continuous output current).
OutputOption A: 1.3A DC current; 0.2A charge current. Option B: 0.8A DC current; 0.7A charge current.
Battery charge capacity2 Ah to 12 Ah (Note Max. battery size/type determined by cabinet size is 3 Ah VRLA)
Max battery size and type2 x 12V 3 Ah VRLA (min. size is 2 x 12V 2 Ah)
IndicatorsSupply Present (Green); General Fault (Amber); Auxiliary Fault (Amber); Hazardous Voltages Present (Red).
ConnectionsMains Input (CONN1); Supply Output (CONN3); Battery Input (CONN3); Fault Relay (CONN4); Charge Off Input (CONN5). Battery Charge Current Link (PLK1); Battery Monitoring On/Off Link (PLK2); High Temp. Output (PL2).
Product dimensions (mm)380 W x 235 H x D 96mm.
Construction & finishPlastic lid and base; RAL7035 textured.
IP RatingIP30 (designed for indoor use only).
Weight1.55kg (without batteries).
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.

Documentation

12 other products in the same category:

Dimensions & Mounting Information

Product dimensions:380 W x 235 H x 96 D mm.
Hole required for flush mounting:367 W x 220 H x 75 D mm. No bezel required.