FF512 MFP 12 Zone Conventional Fire Panel View larger

MFP 12 Zone Conventional Fire Alarm Panel

FF512

New

  • Microprocessor based design.
  • Robust metal enclosure c/w lift off lid & heavy-duty base connections.
  • 12 conventional Zone circuits.
  • 4 conventional Sounder circuits.
  • Separate indicators for open circuit, short circuit, head-out, sounder & battery/power supply faults.
  • Non-latching class change sounder input, latching fire & non-latching fault outputs (via expansion loom).
  • Zone selectable short circuit=fire facility (pre-1980 BS, no resistors in call points).
  • Up to 8 two-wire Repeaters per Main panel.
  • Multi-lingual variants (subject to quantities).
  • Space for 2 x 12V 3.2Ah VRLA batteries.
  • Compatible with virtually all known conventional fire detectors including C-TEC's ActiV range.
  • Designed to comply with BS 5839-4 (this panel in not compliant with EN54-2/4 and should NOT be used in new UK or European installations).

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

CompatibilityDesigned to comply with the requirements of BS5839-4 (with head-out monitoring as standard).
Mains supply230V 50/60Hz.
Mains rated current330mA max.
Internal power supply27V nominal.
Total output current limited to1.4A @ 230V.
Quiescent current75mA (with no mains supply, fault beeper muted, no aux. output connections, EOL devices and resistors only fitted to detector and sounder loops).
Max battery size and type2 x 12V 3.2Ah VRLA connected in series.
No. of detector zone circuits12 (Max. length per circuit is 500m).
Call point resistor value470 to 680Ω.
Max. devices per detector zone20 detectors (max. detector current 2mA). No limit for manual call points.
No. of conventional sounder circuits4 (Max. length per circuit is 500m).
EOL resistor value6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current1.4mA (to all outputs). Outputs are fused at 1A.
Auxiliary relays1 x onboard relay (1A, 30 VDC, follows sounders).
Open collector outputs2 x Fire and 1 x Fault output available via optional FF574X expansion loom. Max. sink current 100mA.
Auxiliary inputsClass change input available via optional FF574X expansion loom.
IndicatorsMains On; Gen Fire; Zone Fire; Zone Fault (S/C, O/C, head out, Zone disabled); Sndr Fault; Processor Fault; Batt/PSU Fault; Aux O/Ps Disabled; Fault Sounder (fault, silenced fire and delayed sounders); OMT; Sounder Walk Test
ControlsExternal (key operated): Reset/Test Scroll; Silence Alarm/Fault Sounders; Evacuate; Disable. Internal: OMT; Sounder Walk Test; Sounder Isolate; Sounder Delay; S/C equals fire; Non-latching zones.
Product dimensions (mm)405 W x 267 H x D 92mm.
Construction & finishMetal lid and base.
IP RatingIP30.
Weight5kg.
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.
NotesOne FF596T repeater transmitter PCB allows the connection of up to eight monitored MFP Repeaters (star or daisy chain wiring, two wires, one for power and one for data).

Documentation

16 other products in the same category:

Dimensions & Mounting Information

Product dimensions:405 W x 267 H x 92 D mm. 
FF385 bezel available for semi-flush mounting.