FF386-2 FP 6 Zone Conventional Fire Panel View larger

FP 6 Zone Conventional Fire Alarm Panel

FF386-2

New

  • Installer-friendly design.
  • Robust metal enclosure c/w lift off lid & heavy-duty base connections.
  • Six conventional Zone circuits.
  • Two conventional Sounder circuits.
  • Separate indicators for open & short circuit fault, sounder fault and battery/power supply fault.
  • Non-latching class change sounder output, latching fire & non-latching fault outputs (via expansion loom).
  • Short circuit=fire facility (pre-1980 BS, no resistors in call points, selectable on a zone by zone basis).
  • Ancillary connections for repeaters & other system add-ons including fault relay modules, fire relay modules, sounder delay relay modules, sounder extender kits, etc).
  • Multi-lingual variants (subject to quantities).
  • Space for 2 x 12V 3.2Ah VRLA batteries.
  • Compatible with virtually all known conventional fire detectors including C-TEC's ActiV range.
  • Designed to comply with BS 5839-4 (this panel in not compliant with EN54-2/4 and should NOT be used in new UK or European installations).

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


Technical Specifications

CompatibilityDesigned to comply with the requirements of BS5839-4 (for head-out monitoring use 1 x BF378M module per zone).
Mains supply230V 50/60Hz.
Mains rated current330mA max.
Internal power supply27V nominal.
Total output current limited to1400mA @ 230V.
Quiescent current60mA (with no mains supply, fault beeper muted, no aux. output connections, EOL devices and resistors only fitted to detector and sounder loops).
Max battery size and type2 x 12V 3.2Ah VRLA connected in series.
No. of detector zone circuits6 (Max. length per circuit is 500m). Additional Zones cannot be added to this panel. For head out monitoring 1 x BF378M is required per Zone.
Call point resistor value470 to 680Ω.
Max. devices per detector zone20 detectors (max. detector current 2mA). No limit for manual call points.
No. of conventional sounder circuits2 (Max. length per circuit is 500m).
EOL resistor value6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current1400mA (to all outputs). Outputs are fused at 1A.
Auxiliary relays1 x onboard relay (1A, 30 VDC, follows sounders). AAdditional relays available via optional expansion looms (FF374FR, FF374FDR & FF374DT).
Open collector outputsAvailable via optional expansion loom FF374X.
Auxiliary inputsAvailable via optional expansion loom FF374X.
IndicatorsMains on; Zone Fire; Zone Fault; Sounder Fault; Battery/Power Supply Fault; O/C fault; S/C fault; Zone isolated; Engineer Test selected.
ControlsReset; Resound; Test Zone Lamps; Evacuate; Silence Alarm Sounders; Silence Fault Sounders; Revert to S/C equals Fire; OMT, Zone Isolate. Keyswitch.
Product dimensions (mm)405 W x 267 H x D 92mm.
Construction & finishMetal lid and base.
IP RatingIP30.
Weight5.0kg.
Operating conditions/temperature-5ºC to +40ºC. Max relative humidity: 95%.
NotesRepeater info: Up to 3 repeaters per main. 5 cores plus 1 per zone. Max. cable length 200m.

Documentation

16 other products in the same category:

Dimensions & Mounting Information

Product dimensions:405 W x 267 H x 92 D mm. 
FF385 bezel available for semi-flush mounting.