Compact W-3-3.1 Wall VAD c/w 91dB(A) Sounder

CA451A/SR

New

  • Certification to EN54-3 (Sounders), EN54-23 (VADs) and 17 (Isolators) by the LPCB pending.
  • Provides 'W-3-3.1' light distribution when wall mounted (min. 0.4 lux over a 3 x 3.1m cuboid area).
  • Can also provide 'C-3-8' light distribution when ceiling mounted (min 0.4 lux over a 3 x 8m cylindrical area).
  • Impressive 91dB(A) sound output @ 1m.
  • Onboard short-circuit loop isolator.
  • 550µA quiescent current.
  • 14mA alarm current @40V DC (VAD lit, sounder on max).
  • Group addressing facility allows multiple devices to be operated simultaneously.
  • 7 selectable volume levels and up to 15 selectable tone pairs.
  • IP21C rated.

  CE

More details

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


More Information

'CAST' is the world’s most-advanced 'distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Now available to purchase, its key features include:

• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) - due 2017.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.

Technical Specifications

Approvals/certificationsCertified to EN54-3, 23 & 17 by the LPCB (pending).
Protocol/compatibilityCompatible with C-TEC's CAST protocol Addressable Fire Panels.
Application/operationProvides W-3-3.1 coverage when wall mounted. Alternatively can be ceiling mounted to provide C-3-8 coverage.
VAD category & coverageW-3-3.1 (30m3 cuboid coverage); C-3-8 (151m3 cylindrical coverage).
Flash rate & colour0.5Hz / White.
Supply/operating voltage20 to 40V DC.
Quiescent current550µA.
Nominal SPL (Sound Pressure Level)91dB(A) when set to tone 1.
Alarm current14mA (VAD lit, Sounder on max).
IndicatorsPolling (green LED) & Short Circuit Isolator Active (amber LED).
Product dimensions (mm)102mm diameter x 63mm deep (not including optional XP95/Discovery and base). Weight: 175g.
IP RatingIP21C (Type A).
Operating conditions/temperature-10ºC to +55ºC. Max. 95% RH (Non-condensing).

Accessories

    1 other products in the same category:

    VAD coverage (with multiplication factors applied)

    VAD coverage depends on factors such as ambient light and viewing angle (direct or indirect). The table below summarises how the coverage of the CA451A/SR increases or decreases based on these factors. To use the table, calculate the lux level of the area requiring coverage, determine whether the viewing angle will be direct or indirect then read off the coverage in the relevant column. For further information refer to our VAD System Design Guide, downloadable from the Documentation tab below.

     Ceiling Mounted Ceiling Mounted Wall MountedWallMounted
    Lux level in area requiring coverageDirect ViewingIndirect ViewingDirect ViewingIndirect Viewing
    000-101 lux8.3m H x 22.4m W3.9m H x 10.4m W15.6m H x 16.12m W5.4m H x 5.58m W
    101-200 lux7.2m H x 19.2m H3.6m H x 9.6m W13.2m H x 13.64m W5.1m H x 5.27m W
    201-300 lux5.7m H x 15.2m W3.0m H x 8.0m W9.6m H x 9.92m W4.2m H x 4.34m W
    301-400 lux4.2m H x 11.2m W2.4m H x 6.4m W6.9m H x 7.13m W3.6m H x 3.72m W
    401-500 lux3.3m H x 8.8m W1.8m H x 4.8m W5.4m H x 5.58m W3.0m H x 3.1m W
    501-600 lux2.7m H x 7.2m W1.5m H x 4.0m W3.9m H x 4.03m W2.7m H x 2.79m W
    601-700 lux2.1m H x 5.6m Wnot applicable3.0m H x 3.1m Wnot applicable
    701-800 lux1.5m H x 4.0m Wnot applicablenot applicablenot applicable