C-TEC CAST CA402 Programmable Heat Detector View larger

CAST Programmable Heat Detector

CA402

New

  • A high quality C-TEC manufactured programmable heat detector for use with C-TEC's XFP & ZFP 'CAST' protocol Addressable Fire Panels.
  • Certified to EN54-5 by Intertek.
  • Can be programmed to operate as a Class A1R (rate of rise), Class A2 (60ºC fixed temperature) or Class B (75ºC fixed temperature) heat detector. Default setting is A2.
  • Onboard short circuit loop isolator.
  • Includes two 8mm x 2mm ultra-bright red LED indicating strips.
  • Different sensitivities can be selected for different times of the day (day/night, building occupied/unoccupied etc).
  • Programmable multi-function status LED.
  • Compatible with C-TEC's CA408 CAST base c/w integrated locking mechanism & ID tag.

LPCB  CE

More details

By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


By buying this product you can collect up to 27 loyalty points. Your cart will total 27 points that can be converted into a voucher of $5.40.


More Information

'CAST' is the world’s most-advanced 'distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Key features include:

• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) - due 2017.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Programmable multi-function status LED.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.

Technical Specifications

Approvals/certificationsCertified to EN54-5 by Intertek (0359-CPR-00184)
CompatibilityCompatible with C-TEC's XFP/ZFP CAST Protocol Addressable Fire Panels.
TypeHeat. Can be programmed as a Class A1R, Class A2 or Class B Heat Detector.
Application temperature25°C typical, 50°C max (in Class A1R and Class A2 mode); 40°C typical, 65°C max (in Class B mode). In A1R mode the detector will also trigger if it detects a sudden rise in temperature.
Static response temperature54°C min, 65°C max (In Class A1R and Class A2 mode); 69°C typical, 85°C max (in Class B mode).
SensitivityOption to set 3 different sensitvity levels at the fire panel. See Operation Modes tab below for details.
Supply wiring2-wire, polarity sensitive.
Supply/operating voltage20 to 40V DC.
Quiescent current60µA @ 24V.
Alarm current6mA (LEDs illuminated).
Indicators2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.
ConnectionsVia CA408 base: 1 +Ve IN (analogue swich); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.
Product dimensions (mm)102.2mm diameter x 37mm deep (detector only); 102.2mm diameter x 57.5mm deep (detector in base).
Construction & finishWhite polycarbonate casing rated to UL94 V-2 with nylon parts.
IP RatingIP42.
Weight99g (not in base); 154g (in base).
Operating conditions/temperature-20ºC to +85ºC.
NotesRequires a CA408 CAST base.

Accessories

    3 other products in the same category:

    Operating Modes

    The modes of operation for this detector, selectable from the XFP or ZFP control panel, are as follows (default setting is Mode 2, Class A2):-

    ModeClassification
    1Class A1R Rate of Rise (Application temp: 25°C typical, 50°C max; Static response temp: 54°C min, 65°C max; will also trigger if it detects a sudden rise in temperature).
    2Class A2 60ºC Fixed Temperature (Application temp: 25°C typical, 50°C max; Static response temp: 54°C min, 65°C max)
    3Class B 75ºC Fixed Temperature (Application temp: 40°C typical, 65°C max ; Static response temp: 69°C typical, 85°C max)

    Approval Certificates

    Approval Certificate (Intertek)

    Download

    EC Certificate of Conformity (CPR)

    Download

    Declaration of Performance (C-TEC)

    Download